鄂尔多斯KYN28-12 Armored Removable AC Metal Enclosed Switchgear

KYN28-12 indoor AC armored removable metal-enclosed switchgear. It is suitable for three-phase AC rated voltage 12kV, rated frequency 50Hz power system, used to receive and distribute electric energy and control, protect and monitor the circuit.

Product Description

Overview

KYN28-12 indoor AC armored removable metal-enclosed switchgear. It is suitable for three-phase AC rated voltage 12kV, rated frequency 50Hz power system, used to receive and distribute electric energy and control, protect and monitor the circuit.
This product complies with the requirements of GB3906 "3-35kV AC Metal-enclosed Switchgear", GB/T11022 "Common Technical Requirements for High-voltage Switchgear and Control Equipment Standards", IEC60298 "Rated Voltage 1kV Above 52kV and Below AC Metal-enclosed Switchgear and Control Equipment", DL/T404 "Technical Conditions for Indoor AC High-voltage Switchgear Ordering".

 

Model Meaning

H Y N 28 - 12 / - Z
Metal armored Removable Indoor Design No.   Rated voltage (KV)   Rated current (KV)   Vacuum circuit breaker


 

Conditions of use
• Ambient temperature: maximum temperature +40°C, minimum temperature -15%C (can reach -45°C under special process);
• Ambient humidity: daily average <95%. Monthly average ≤90%;
• Altitude: below 1000m;
• Earthquake resistance: earthquake intensity does not exceed 8 degrees;
• The surrounding air should not contain obvious pollution such as corrosive or flammable gas and water vapor;
• No serious dirt and frequent severe vibration, the harshness design under harsh conditions meets Class 1 requirements;
• When used under normal environmental conditions exceeding those specified in GB3906, the user and the manufacturer shall negotiate.
Note: ① When the relative humidity is greater than 70%, the electric heater should be turned on. ② Where the altitude exceeds 1000m, it shall be handled in accordance with the provisions of JB/Z102-71.

 

Main technical parameters

project Unit Parameter
Rated voltage kV 3.6、7.2、12
Rated frequency Hz 50
Circuit breaker rated current A 630、1250、1600、2000、2500、3150
Switch cabinet rated current A 630、1250、1600、2000、2500、3150
Rated dynamic stability current (4s) kA 16、20、25、31.5、40、50
Rated stability current (peak value) kA 40、50、63、80、100、125
Rated short-circuit breaking current kA 16、20、25、31.5、40、50
Rated short-circuit closing current (peak value) kA 40、50、63、80、100、125
Rated insulation level 1 min power frequency withstand voltage kV 24 32 42
Lightning impulse withstand voltage 40 60 75
Protection level   Housing IP4X, isolation room, circuit breaker room door open IP2X

 

VD4, VS1-12 Vacuum circuit breaker technical parameters

project Unit Parameter
Rated voltage kV 12
Rated frequency Hz 50
Circuit breaker rated current A 630、1250、1600、2000、2500、3150
Rated dynamic stability current (4S) A 16、20、25、34.5、40、50
Rated stability current (peak value) kA 40、50、63、80、100、125
Rated short-circuit breaking current kA 16、20、25、34.5、40、50
Rated short-circuit closing current (peak value) kA 40、50、63、80、100、125
Rated insulation level 1 min power frequency withstand voltage kV 42
Lightning impulse withstand voltage 75
Rated operating sequence    
Rated short-circuit breaking current breaking times Second-rate 50
Mechanical life Second-rate 200

 

Mechanical characteristics of VD4 and VS1 vacuum circuit breakers

project Unit Parameter
Contact opening distance mm 11±01
Overtravel mm 4±0.5
Phase center distance mm 210±0.5,275±0.5
Closing contact bounce time ms ≤2
Three-phase opening phase difference ms ≤2
Breaker time
When the operating voltage is
Maximum ms ≤50
Rated ms ≤50
Minimum ms ≤50
Closing time ms ≤60
Average closing speed m/s 0.9-1.2
Average opening speed m/s 0.6-0.8

When the circuit breaker is used to control a 3~10kV motor, if the starting current is less than 600A, a metal zinc oxide lightning arrester must be added. The specific requirements are negotiated between the user and our company: When the circuit breaker is used to disconnect a capacitor bank, the rated current of the capacitor should not be greater than 80% of the rated current of the circuit breaker.

 

Operating mechanism technical parameters

project Unit Parameter
Rated operating voltage Closing coil V AC/DC220,110
Opening coil V AC/DC220,110
Coil power Closing coil W 245
Opening coil W 245
Energy storage motor power W 50
Energy storage motor rated voltage V AC/DC220,110
Energy storage time S ≤10

 

Overall installation dimensions (mm)

XX