Sweden YB-12/0.4 Outdoor prefabricated substation (European style)
Category:
Product Description
Overview
YB-12 series outdoor prefabricated substation (European style) is a high-voltage switchgear distribution transformer and low-voltage distribution device, which are prefabricated indoor and outdoor compact distribution equipment arranged in a certain wiring scheme, that is, the functions of high-voltage power receiving, transformer, low-voltage distribution, etc. are organically combined together, and installed in a moisture-proof, rust-proof, dust-proof, rat-proof, fire-proof, anti-theft, gasketed, fully enclosed, movable steel structure or non-metallic box, and the mechatronics is fully enclosed and operated;
It is widely used in urban power grid transformation, residential areas, high-rise buildings, factories and mines, hotels, shopping malls, airports, railways, oil fields, docks, highways and temporary power facilities and other indoor and outdoor places.
Model meaning
| YBD | 口 | - | 12/0.4 | - | 口 |
| Prefabricated substation | Design No. | Rated voltage (high voltage/low voltage) |
|
Transformer capacity |
Conditions of use
• Altitude ≤1000m;
• The upper limit of the ambient temperature of the surrounding air temperature is +40°C, and the lower limit is -25%C;
• Relative humidity: the daily average value is not greater than 95%, and the monthly average value is not greater than 90%;
• Installation location: a location free of fire, explosion hazards, conductive dust, chemically corrosive gases and severe vibration; .
• When the above normal usage conditions cannot meet the usage requirements, the user shall negotiate with the manufacturer.
Main technical parameters
| project | 单位 | High voltage electrical appliances | transformer | Low voltage electrical appliances |
| Rated voltage | kV | 6/10 | 60/0.4 10/0.4 | 0.4 |
| Rated capacity | kVA | 50-1600 | ||
| Rated current | A | 200、400、630 | 100-3200 | |
| Rated short-circuit breaking current | A | Circuit breaker 25kA | 15~63kA | |
| kA | Combination switch depends on fuse | |||
| Rated short-time withstand current | kA | 16,20 (4S) | 15(1S) | |
| 30(1S) | ||||
| Rated peak withstand current | kA | 31.5, 50 | 30 | |
| 63 | ||||
| Power frequency withstand voltage (1min) | kV | Phase to ground and phase to phase 32/42 | 25/35(Oil immersion) | ≤0.3,2 |
| Isolation break 36/48 | 20/28(Dry) | >0.3,2.5 | ||
| Lightning impulse withstand voltage (peak) | kV | Phase to ground and phase to phase 60/75 | 60/75 | |
| Isolation break 70/85 | ||||
| Box protection level | IP33 | |||
| Noise level | db | ≤45 | ||
| Implementation standard | GB/T 17467 "High-voltage and low-voltage prefabricated substations" | |||
| DL/T537 "6-35kV Box-type Substation Ordering Technical Conditions" |