Singapore XGN-12(Z) Box-type fixed AC metal-enclosed switchgear

XGN-12(Z) box-type fixed AC metal-enclosed switchgear (hereinafter referred to as switchgear) is a new generation of high-voltage electrical complete set products of our company, which meets the requirements of national standard GB3906 "-35kV AC metal-enclosed switchgear" and Ministry of Electric Power DLT404 "Technical Conditions for Ordering Indoor AC High-voltage Switchgear", and also meets the international standard IEC60298 "Requirements for AC metal-enclosed switchgear and control equipment above 1kV and below 52kV".

Product Description

Overview

XGN-12(Z) box-type fixed AC metal-enclosed switchgear (hereinafter referred to as switchgear) is a new generation of high-voltage electrical complete set products of our company, which meets the requirements of national standard GB3906 "-35kV AC metal-enclosed switchgear" and Ministry of Electric Power DLT404 "Technical Conditions for Ordering Indoor AC High-voltage Switchgear", and also meets the international standard IEC60298 "Requirements for AC metal-enclosed switchgear and control equipment above 1kV and below 52kV".
This product absorbs advanced foreign technology. It is small in size, only 50% of the volume of ordinary switch cabinets. The circuit breaker has high reliability and good performance; the "five-protection" interlocking mechanism is reliable and simple. The switch cabinet is an indoor complete set of 3.6, 7.2, 12kV three-phase AC 50Hz single busbar segmented equipment for receiving and distributing electric energy. It also has the functions of controlling, protecting and monitoring the circuit, and can be used in various types of power plants, substations, industrial and mining enterprises, high-rise buildings and other places. It can also be combined with ring network cabinets for use in switchgear.

 

Model meaning

X G N - 12 Z
Box type switchgear Fixed Indoor Design No.   Rated voltage (KV) Vacuum switch


 

Conditions of use
• Altitude not exceeding 1000m;
• Ambient temperature: -25°C ~ +409C, average temperature within 24 hours not exceeding +35*C;
• Horizontal inclination: not more than 3°;
• Earthquake intensity: not more than 8 levels;
• No severe vibration, impact or explosion hazard.

 

Main technical parameters

project Unit Parameter
Rated voltage kV 3.6、7.2、12
Rated power frequency withstand voltage kV To ground, phase to phase: 42; break: 48
Rated lightning impulse withstand voltage kV To ground, phase to phase: 75; break: 85
Rated frequency Hz 50
Rated current A 630、1250
Rated short-circuit breaking current (effective value) kA 20、25、31.5
Rated short-circuit closing current (peak value) kA 50、63、80
Rated dynamic stability current (peak value) kA 50、63、80
Rated thermal stability current 4s (effective value) kA 20、25、31.5
Protection level   IP2X
Dimensions (width x depth x height) mm 900×1000×2300
Weight kg

≈600

 

 

Main features
• The cabinet is welded with high-quality angle steel;
• The circuit breaker room is located in the middle (lower) part of the cabinet, which is easy to install, debug and maintain. It is equipped with VS1 circuit breaker as standard and is equipped with a pressure release channel to ensure personal safety
• It adopts advanced and reliable rotary isolating switch, which can safely enter the circuit breaker room for maintenance when the main bus is energized;
• The protection level of the whole cabinet is IP2X;
• It is equipped with a reliable and fully functional mandatory mechanical locking device, which can easily and effectively meet the "five protection" requirements;
• It has a reliable grounding system;
• An observation window is installed on the door, and the working status of the components in the cabinet can be clearly observed:
• The operating mechanism lock adopts the XGN locking mechanism used in the XGN2-12 cabinet, which is simple, reliable, convenient and practical;
• The incoming and outgoing cables are lower than the front of the cabinet, which is convenient for users to connect.

 

Main technical parameters of VS1-12 vacuum circuit breaker

project Unit Parameter
Rated voltage kV 12
Rated current A 630、1250
Rated short-circuit breaking current kA 20、25、31.5
Rated short-circuit closing current kA 50、63、80
Rated short-time withstand current (4s effective value) kA 20、25、31.5
Rated peak withstand current (peak value) kA 50、63、80
Mechanical life Second-rate 10000
Rated short-circuit breaking current breaking times Second-rate 50
Rated operation sequence   Open-0.3s-Close-Open-180s-Close-Open
Contact opening distance mm 11±1
Contact travel mm 4±0.5
Phase center distance mm 210
Opening speed m/s 1.2±0.2
Closing speed m/s 0.6±0.2
Opening time ms ≤60
Closing time ms ≤75
Three-phase opening synchronism ms ≤2
Closing bounce ms ≤2
Circuit resistance µΩ ≤45
Contact cumulative allowable wear thickness mm 3

Note: For the technical parameters of other electrical components, please refer to their respective instruction manuals. The solution for switch cabinet with rated current greater than 1600A must be negotiated with our company.

 

Structural features(mm)

Structural features(mm)

1. Cabinet door 2. Lighting lamp 3. Observation window 4. Operating mechanism 5. Small door panel 6. Instrument door 7. Eyebrow 8. Busbar wall bushing 9. Bolt 10. Washer 11. Washer 12. Nut 13. Disconnector 14. Pull rod 15. Rear cover 16. Current transformer 17. Vacuum circuit breaker 18. Disconnector 19. Sensor 20. Bolt 21. Washer 22. Washer 23. Frame 24. Lightning arrester

Installation
• Refer to the figure below for the installation foundation. The foundation channel steel protrudes 1-3mm from the ground. The unevenness within each meter should not exceed 1.5m and the total length should not exceed 5mm.
• Place the switch cabinet on the foundation in order and adjust the installation position. Then fix it with M12 bolts or spot welding, and tighten the cabinets with M8 bolts.
• Remove the rear cover to install the main busbar and secondary cable. The terminal contact surface should be cleaned and coated with neutral vaseline. After installation, make sure to seal the primary cable hole.
• Connect the inter-cabinet grounding busbar to form a body along the arrangement direction of the switch cabinet. Check whether the working grounding and protective grounding are missing, whether the grounding loop is continuously conductive, and the working grounding resistance should be no more than 1000µΩ, and the protective grounding resistance should be no more than 40.
• Install the secondary cable. The cable is introduced from the bottom of the front of the cabinet, enters the low-voltage room along the side wall, and is tapped on the terminal block; or introduced from the secondary busbar on the top of the cabinet into the low-voltage room, and the cable hole is sealed after installation.
• Clean the dust and debris in the cabinet.