Australia HLX-AC Photovoltaic AC Combiner Box
Category:
Product Description
HLX photovoltaic grid-connected box is suitable for photovoltaic string power generation system, which is an important power protection part connecting string inverter and grid system. The circuit protection part adopts photovoltaic grid-connected circuit breaker and pull-ring isolating switch, and adopts secondary lightning protection. The protection level is IP65, which is the same as string inverter, and meets the requirements of outdoor installation, waterproof, dustproof, UV protection, salt spray corrosion, etc. The internal structure of this product is simple and clear, and the wiring is neat and reasonable. High reliability and simple maintenance. Outdoor wall-mounted installation can adapt to various harsh environments.
In addition to standard materials and sizes, it can be customized according to user requirements.
Main technical parameters:
| Product Model | HLX-AC4/1 | HLX-AC6/1 | HLX-AC8/1 |
| Number of input channels | 4 | 6 | 8 |
| Maximum input voltage | AC690 | AC690 | AC690 |
| Input current per channel | 0~100A | ~100A | ~100A |
| Maximum output current | 250A | 400A | 630A |
| Rated working voltage Un | 480VAC | 480VAC | 480VAC |
| Voltage protection level Up | ≤3.2kV | ≤3.2kV | ≤3.2kV |
| Nominal flow capacity In( 8/20us) | 20kA (optional according to customer requirements) | ||
| Maximum flow capacity Imax( 8/20 us) | 40kA (optional according to customer requirements) | ||
| Response time | <25ns | ||
| Temperature and humidity | Working temperature: -40-+85C, humidity 95%, no condensation, no corrosive gas environment | ||
| altitude | ≤4000m | ||
| Input and output switch | breaker | ||
| Surge protector | Standard | ||
| Box material | Hot dip galvanized steel sheet / stainless steel / cold rolled steel sheet / engineering plastics | ||
| Box protection level | IP65 | ||
| Cable connector protection level | IP66 | ||
| Volume (width x height x depth) mm | 800x600mmx200mm | 800mmx800mmx200mm | 800mmx1000mmx200mm |
Main features
• The exposed live parts inside are protected by flame-retardant, anti-static, and high-temperature resistant transparent covers;
• The incoming and outgoing circuit breakers are installed vertically and laid flat on the box, and the wiring corresponds to each other to avoid wrong connection
• The main line is connected by copper busbars, and the surface of the copper busbars is tinned for corrosion and oxidation prevention;
• Each phase line is marked with the common color in the industry, which is clear and eye-catching;
• Optional intelligent monitoring system (system voltage, main current, switch status, lightning protection status);
• Applicable to various voltage levels in the industry: 380Vac, 480Vac. 540Vac;
• Rain cover design, outdoor installation.