Products

Products

PRODUCTS CENTER

Argentina YB-12/0.4 Outdoor prefabricated substation (European style)

YB-12 series outdoor prefabricated substation (European style) is a high-voltage switchgear distribution transformer and low-voltage distribution device, which are prefabricated indoor and outdoor compact distribution equipment arranged in a certain wiring scheme, that is, the functions of high-voltage power receiving, transformer, low-voltage distribution, etc.

Product Description

Overview

YB-12 series outdoor prefabricated substation (European style) is a high-voltage switchgear distribution transformer and low-voltage distribution device, which are prefabricated indoor and outdoor compact distribution equipment arranged in a certain wiring scheme, that is, the functions of high-voltage power receiving, transformer, low-voltage distribution, etc. are organically combined together, and installed in a moisture-proof, rust-proof, dust-proof, rat-proof, fire-proof, anti-theft, gasketed, fully enclosed, movable steel structure or non-metallic box, and the mechatronics is fully enclosed and operated;
It is widely used in urban power grid transformation, residential areas, high-rise buildings, factories and mines, hotels, shopping malls, airports, railways, oil fields, docks, highways and temporary power facilities and other indoor and outdoor places.

 

Model meaning

YBD - 12/0.4 -
Prefabricated substation Design No.   Rated voltage (high voltage/low voltage)

 

Transformer capacity


 

Conditions of use
• Altitude ≤1000m;
• The upper limit of the ambient temperature of the surrounding air temperature is +40°C, and the lower limit is -25%C;
• Relative humidity: the daily average value is not greater than 95%, and the monthly average value is not greater than 90%;
• Installation location: a location free of fire, explosion hazards, conductive dust, chemically corrosive gases and severe vibration; .
• When the above normal usage conditions cannot meet the usage requirements, the user shall negotiate with the manufacturer.

 

Main technical parameters

project 单位 High voltage electrical appliances transformer Low voltage electrical appliances
Rated voltage kV 6/10 60/0.4  10/0.4 0.4
Rated capacity kVA   50-1600  
Rated current A 200、400、630   100-3200
Rated short-circuit breaking current A Circuit breaker 25kA   15~63kA
kA Combination switch depends on fuse  
Rated short-time withstand current kA 16,20 (4S)   15(1S)
30(1S)
Rated peak withstand current kA 31.5, 50   30
63
Power frequency withstand voltage (1min) kV Phase to ground and phase to phase 32/42 25/35(Oil immersion) ≤0.3,2
Isolation break 36/48 20/28(Dry) >0.3,2.5
Lightning impulse withstand voltage (peak) kV Phase to ground and phase to phase 60/75 60/75  
Isolation break 70/85  
Box protection level     IP33  
Noise level db   ≤45  
Implementation standard   GB/T 17467 "High-voltage and low-voltage prefabricated substations"    
DL/T537 "6-35kV Box-type Substation Ordering Technical Conditions"